Safety engineering

dimensioned drawing


Manual fire alarm
[Type C31]
The C31 can be used outside and in moist spaces as a surface mount. The highly flame resistant plastic casing is UV resistant. The easily replaceable glass panels consist of colourless thin sheet glass. The alarm button is locked as soon as it is pressed, and can only be reset using the covered reset lever. The C31 is available in the standard colours red, yellow or blue. By request we will also deliver this manual fire alarm in other colours
Technical data | ||
Storage temperature | -40°C … +70°C | |
Operating temperature | -35°C … +60°C | |
Casing enclosure | IP 66 | |
Type approval | red | VDS G 206113 / 0786-CPD-20309 |
yellow | VDS G 207079 / 0786-CPD-20310 | |
blue | VDS G 207099 / 0786-CPD-20311 | |
Contact rating | 0.5-30 V/0,1 A | |
LED rating | 5-15 mA | |
Terminal plugs | 0.08-2.5 mm2 | |
Material | PC |
Model | Order no. |
without resistor | 51.11 _ |
threshold fire alarm system | 51.13 _ |
red = 0/yellow = 1/blue = 2/green = 3/orange = 4(withoutLED) | _ |
red = 5/yellow = 6/blue = 7/green = 8/orange = 9 (with LED) | |
Metal key for front door | 50.18001 |
Glass panel 10pc/PU | 5111000.03.40B2 |
Dimensions:
135 (length) x 135 (width) x 61 (height) mm
Cable gland:
2 x M20 x 1.5, Ø 6-12 mm
Weight:
approx. 475
Download
C31-eng
VDS-G-206113-CE-0786-CPD-20309
VDS-G-207079-CE-0786-CPD-20310
VDS-G-207099-CE-0786-CPD-20311