Safety engineering

dimensioned drawing



Ex manual alarm call point
[Type dC31]
The manual call point, type dC31, was developed for explosion hazard areas, where gas or dust can cause an explosive atmosphere. The device provides a maximum security, without using a safety barrier. According to a free choice of different resistors, at a threshold alarm system, the detector can be used at several fire alarm systems. The impact resistant chassis is available on stock in five different colours. The easily replaceable glass panel consist of flat, colourless thin sheet glass.
Technical data |
||
Storage temperature: | -35°C – +60°C | |
Operation temperature: | -20°C – +60°C | |
Casing enclosure: | IP 66 | |
Ignition protection class: | ![]() |
II2G Ex emb IIC T6 Gb |
II2D Ex tb IIIC T80°C Db | ||
Ex type approval: | BVS 09 ATEX E 016 X | |
Type approval: | red | VDS G 206113 / 0786-CPD-20309 |
yellow | VDS G 207079 / 0786-CPD-20310 | |
blue | VDS G 207099 / 0786-CPD-20311 | |
Rated voltage: | 0,5 – 30 V | |
Rated current: | In < 0,1A / Ik < 4,5A | |
Connection terminals: | 0,08-2,5 mm² | |
Material: | PC |
Model | Order no. |
change over contact | 55.11 _ |
threshold fire alarm system | 55.13 _ |
red = 0 /yellow = 1 /blue = 2 /green = 3 /orange = 4 | _ |
Metal key for front door | 50.18001 |
Glass panel 10pc/PU | 5111000.03.40B2 |
Spring button warning device available on request.
Dimensions:
135 (length) x 135 (width) x 61 (height) mm
Cable gland:
2 x M20 x 1.5 (Ø 6-12 mm)
Weight:
500 g
Download
dC31-eng
bvs-09-atex-e-016x-eng.pdf
VDS-G-206113-CE-0786-CPD-20309
VDS-G-207079-CE-0786-CPD-20310
VDS-G-207099-CE-0786-CPD-20311